| Liebert® NXC offers reliable and flexible secure power in a fully integrated package solution. Its highly efficient transformer-free double conversion technology delivers installation and running cost savings. The Liebert® NXC range has been designed to optimize specific rating requirements, thus enhancing flexibility and installation space needs. | |
| Features | |
| UPS topology | Double-conversion (Online) |
| Output power capacity | 40 kVA |
| Output power | 40000 W |
| Input operation voltage (min) | 380 V |
| Input operation voltage (max) | 415 V |
| Input frequency | 50/60 Hz |
| Input power factor | 0.99 |
| Overload capacity (5 minute) | 125% |
| Overload capacity (1 minute) | 150% |
| Output voltage Total Harmonic Distortion (THD) | 2% |
| Input current Total Harmonic Distortion (THD) | 5% |
| Noise level | 58 dB |
| Design | |
| Form factor | Tower |
| Product colour | Black |
| Display type | LCD |
| International Protection (IP) code | IP20 |
| Certification | EN/IEC/AS 62040-1, EN/IEC/AS 62040-2, VFI-SS-111 |
| Weight & dimensions | |
| Width | 600 mm |
| Depth | 850 mm |
| Height | 1600 mm |
| Other features | |
| Bypass | Bypass voltage tolerance (%) selectable from +20 to -40 Bypass frequency tolerance (%) ±20 (±10 selectable) |
Every effort has been made to ensure the accuracy of all information contained herein. e-nitiative shall not be liable for any changes resulting in wrong product description, tax code and/or price. The shown information (specifications, prices, taxes) should be considered as an indication and can be changed at any moment and without any prior notice.