Introduction | |
---|---|
Built-in Web/SNMP management Full-featured management via a Web browser as well as comprehensive management from a Network Management System. Environmental monitoring Prevent equipment failure from a full range of threatening environmental conditions. Audible alarms Provides notification of changing utility power and UPS power conditions LCD graphics display Text and mimic diagrams that display modes of operation, system parameters and alarms. Multiple levels of service With the option of packages or individual service components, our services are structured to allow you to pick and choose what you would like APC to do for you. 7x24 telephone technical support Our experienced technical support engineers are available to answer your questions, giving you peace of mind knowing the help you need is there when you need it. Front-access servicing Simplifies installation and UPS maintenance while minimizing space requirements. User-replaceable air filters Enables quick and simple replacement of air filters. Battery replacement without tools Enables fast battery replacement, lowering Mean Time to Repair (MTTR). Excellent footprint Small UPS footprint provides maximum usage of valuable electrical room floorspace Input power factor correction Minimizes installation costs by enabling the use of smaller generators and cabling. Temperature-compensated battery charging Prolongs battery life by regulating the charge voltage according to battery temperature. Advanced electrical features Excellent power conditioning, very low harmonic distortion through IGBT rectifier, input power factor correction, and high power efficiency Frequency and voltage regulation Gives higher application availability by correcting poor frequency and voltage conditions without using the battery. Generator compatible Ensures clean, uninterrupted power to protected equipment when generator power is used. Automatic internal bypass Supplies utility power to the connected loads in the event of a UPS power overload or fault. Hot-swappable batteries Ensures clean, uninterrupted power to protected equipment while batteries are being replaced Parallel-capacity capable Increases total power capacity by using multiple uninterruptible power supplies simultaneously. Dual mains input Increases availability by allowing the UPS to be connected to two separate power sources. EU CoC for UPS Ensures that UPSs sold in the EU are highly efficient |
|
Features | |
Input operation voltage (min) | 220 V |
Input operation voltage (max) | 400 V |
Design | |
Product colour | Grey |
Certification | EN 50091-2, EN/IEC 62040-1-1, EN/IEC 62040-3, VFI-SS-111 |
Operational conditions | |
Operating temperature (T-T) | 0 - 40 °C |
Storage temperature (T-T) | -15 - 45 °C |
Operating relative humidity (H-H) | 0 - 95% |
Storage relative humidity (H-H) | 0 - 95% |
Operating altitude | 0 - 3000 m |
Non-operating altitude | 0 - 9000 m |
Weight & dimensions | |
Width | 1010 mm |
Depth | 800 mm |
Height | 120 mm |
Weight | 100 kg |
Package width | 1200 mm |
Package depth | 800 mm |
Package height | 1600 mm |
Package weight | 120 kg |
Other features | |
Output connections | (1) Hard Wire 3-wire (H N + G) (Battery Backup) |
Every effort has been made to ensure the accuracy of all information contained herein. e-nitiative shall not be liable for any changes resulting in wrong product description, tax code and/or price. The shown information (specifications, prices, taxes) should be considered as an indication and can be changed at any moment and without any prior notice.