Introduction | |
---|---|
InfraStruXure Central compatible Enables centralized management via APC InfraStruXureŽ Central. Smallest footprint Minimizes your real estate expenses Top and bottom cable entry (standard) Flexibility that allows the customer to decide - and at no extra cost. UL-listed Touch-safe backplane Adding Power Distribution Modules requires no hot work; one trained user can safely add new modules without removing power to the existing PDU load Multiple distribution options Superior design flexibility enables a wide range of customer requirements to be addressed. Toolless installation of breakers Install factory-assembled Power Distribution Modules in under ten minutes - no tools are required Safety Enhance user safety with isolation at all touch points and with positive locking mechanisms that reduce the risk of accidental disconnection |
|
Ports & interfaces | |
Input connection type | Hard Wire 5-wire (3PH + N + G) |
Output connections | 2x Hard Wire 5-wire (3PH + N + G) |
Features | |
Certification | CE, FCC 15 A |
Power | |
Nominal input voltage | 400 V |
Load capacity | 160000 VA |
Maximum input current per phase | 295 A |
Weight & dimensions | |
Dimensions (WxDxH) | 600 x 1070 x 1991 mm |
Weight | 411.8 kg |
Packaging data | |
Package dimensions (WxDxH) | 848 x 1210 x 2150 mm |
Package weight | 444.6 kg |
Operational conditions | |
Operating temperature (T-T) | 0 - 40 °C |
Storage temperature (T-T) | -15 - 40 °C |
Operating relative humidity (H-H) | 0 - 95% |
Storage relative humidity (H-H) | 0 - 95% |
Every effort has been made to ensure the accuracy of all information contained herein. e-nitiative shall not be liable for any changes resulting in wrong product description, tax code and/or price. The shown information (specifications, prices, taxes) should be considered as an indication and can be changed at any moment and without any prior notice.