Introduction | |
---|---|
Manageability Integrated network management Provides complete remote monitoring and control of the UPS. Enables you to monitor remote UPS's from a web browser or industry standard Network Management System. Convenience Easy to install Innovative design allows for fast, easy installation by almost anybody. Economy Cost of acquisition Designed to provide an optimized price/performance ratio, a number of exceptional features have been carefully selected to optimize both performance and cost benefits. Serviceability Front-access servicing Simplifies installation and UPS maintenance while minimizing space requirements. 5x8 Start-up service included Required for full coverage of factory warranty Availability Wide input voltage range Designed for harsh electrical environments to save battery life. Dual feed input Allows installation of two independent power sources with the option of hot stand-by configuration to provide redundancy for mission critical applications. Double conversion on-line topology Guarantees a consistently high level of power quality. Any disturbances on the distribution waveform are regenerated via the zero transfer time AC to DC then DC to AC conversion process. The battery is only used as a back-up source. Parallel-redundant capable Power the connected equipment with multiple uninterruptible power supplies to increase system redundancy |
|
Features | |
UPS topology | Double-conversion (Online) |
Output power capacity | 10 kVA |
Output power | 8000 W |
Waveform | Sine |
Input operation voltage (min) | 323 V |
Input operation voltage (max) | 477 V |
Input frequency | 45/65 Hz |
Output operation voltage (min) | 220 V |
Output operation voltage (max) | 240 V |
Maximum current | 65 A |
Number of input phases | 3 |
Number of output phases | 1 |
Efficiency | 91.8% |
Input power factor | 0.94 |
Crest factor | 2.5:1 |
Emergency Power Off (EPO) | Y |
Output voltage Total Harmonic Distortion (THD) | 3% |
Surge protection | Y |
Power protection features | Overload |
Web-based management | Y |
Ports & interfaces | |
Power plug | Terminal |
AC outlets quantity | 3 AC outlet(s) |
Emergency Power Off (EPO) connector | Y |
Battery | |
Battery technology | Sealed Lead Acid (VRLA) |
Battery voltage | 192 V |
Battery recharge time | 10 h |
Design | |
Form factor | Tower |
Product colour | Grey |
Display type | LED |
LED indicators | Status, Battery replacement |
Certification | CE, EN/IEC 62040-1-1, EN/IEC 62040-2, EN/IEC 62040-3, IEC 61000-4-5, IEC 62040-2, TUV, VFI-SS-111 |
Operational conditions | |
Operating temperature (T-T) | 0 - 35 °C |
Storage temperature (T-T) | -10 - 60 °C |
Operating relative humidity (H-H) | 0 - 95% |
Storage relative humidity (H-H) | 0 - 95% |
Operating altitude | 0 - 3000 m |
Non-operating altitude | 0 - 9000 m |
Technical details | |
Sustainability certificates | RoHS |
Weight & dimensions | |
Width | 400 mm |
Depth | 860 mm |
Height | 1300 mm |
Weight | 320 kg |
Package width | 800 mm |
Package depth | 965 mm |
Package height | 1440 mm |
Package weight | 354 kg |
Packaging data | |
Quick installation guide | Y |
Resource CD | Y |
Other features | |
Number of phases | 3 |
Every effort has been made to ensure the accuracy of all information contained herein. e-nitiative shall not be liable for any changes resulting in wrong product description, tax code and/or price. The shown information (specifications, prices, taxes) should be considered as an indication and can be changed at any moment and without any prior notice.